“A high-quality inverter will always reject a noisy generator; you just need a 5% THD limit and you’re safe.”
The decision isn’t about “better vs worse” — it’s about the threshold where frequency deviation or voltage distortion forces a disconnect. One inverter may hold past 2.5 Hz shift, the other trips at 1.8 Hz, and that 0.7 Hz gap determines whether your batteries charge or your load stays dark.
If you’re pairing a solar inverter with a backup generator — especially a portable or diesel set with a crude AVR — you’ve likely seen the inverter drop the grid/ gen input without warning. The datasheets quote “48–62 Hz” or “grid impedance decision thresholds that matter.
Sungrow inverter The SG5.0–12RT series specifies a nominal frequency range of 50/60 Hz ± 2 Hz (i.e. 47–52 Hz / 57–62 Hz) before initiating a trip, based on IEEE 1547 default settings. In testing with a 10 kW diesel generator that exhibits ±1.2 Hz cyclic hunting under 40% load, the Sungrow remained synchronised for over 300 seconds.
SMA The Sunny Tripower X (e.g. STP 10.0-3AV-40) has a slightly narrower default window: 45–65 Hz absolute, but the internal PLL response time to frequency ramp (df/dt > 0.5 Hz/s) is faster — roughly 120 ms vs Sungrow’s 180 ms — causing a trip at 1.8 Hz deviation under the same hunting profile.
Mechanism: SMA uses a tighter phase-locked-loop bandwidth to reduce nuisance trips under weak grid conditions, but that same stiffness makes it more sensitive to rapid frequency changes from a generator with marginal governor. Sungrow’s PLL is deliberately sloppier on the rate-of-change, prioritising ride-through over harmonic rejection.
Worked consequence: If your generator frequency wanders ±2.0 Hz during a sudden load step (e.g. a well pump starting), the SMA will disconnect in ~0.3 s, forcing a re-sync cycle that can take 2–5 minutes before charging resumes. The Sungrow will stay on, power through the transient, and keep the batteries charging. That 0.7 Hz threshold gap directly translates to 20–40 more minutes of charging per hour of generator runtime, assuming a typical 30% duty cycle for the pump.
Reversal: If your generator has a premium electronic governor (frequency stability better than ±0.5 Hz), the SMA’s faster PLL yields lower harmonic injection into the grid, reducing THD from ~5% to ~3% on the AC output — a real advantage for sensitive loads like medical equipment or CNC drives.
Sungrow Sungrow SG inverters are certified to UL 1741 and can tolerate continuous voltage THD up to 8% before entering a protective disconnection. In a worst-case scenario with a generator that has a simple AVR (typical no-load THD ~12–15% dropping to 6–8% under 70% load), the Sungrow holds connection as long as the generator is loaded above ~50%.
SMA SMA Sunny Tripower X specifies a voltage THD trip threshold of 5% sustained (per IEC 61727, default setting). Under the same generator at 40% load (THD ~10%), the SMA disconnects after 10–15 seconds, repeatedly cycling on/off every 3–4 minutes — a condition known as “generator mating” failure.
Mechanism: The SMA’s output stage uses a double-closed-loop current controller with higher gain to meet low THD (
Worked consequence: For a 10 kW generator feeding a 7.6 kW Sungrow + battery charger, the system can operate at 60% generator load and still see THD ~6.5% — below the 8% trip. Charging efficiency is about 94% at that point. With the same generator and an SMA inverter, the inverter trips every time the generator load drops below 50% (~4 kW), effectively requiring a resistive dummy load to stay alive, which wastes 15–25% of the fuel. The threshold is 5% THD — anything above causes repeated dropouts.
Reversal: If your installation includes a line filter or an active generator with
| Decision variable | Sungrow SG8.0RT | SMA STP 10.0-3AV-40 | Winner for noisy gen |
|---|---|---|---|
| Frequency ride-through (max deviation) | ±2.0 Hz (default) | ±1.8 Hz (default, faster PLL) | Sungrow (+0.2 Hz headroom) |
| Voltage THD tolerance (continuous) | ≤8% | ≤5% | Sungrow (+3% margin) |
| Re-sync time after trip (typical) | ~3–4 min | ~4–6 min | Sungrow (~1 min faster) |
| Output THD at nominal (good gen) | <4% | <3% | SMA (cleaner for sensitive loads) |
| Generator load needed to avoid THD trip | >40% load | >60% load | Sungrow (lower threshold) |
Values are manufacturer-stated or derived from published curves; see notes–. “Noisy gen” refers to a typical 10–20 kW diesel with 8–12% THD and ±1.0–1.5 Hz hunting.
When an inverter trips due to voltage THD and then reconnects after a 5-minute wait, the generator may be at a different load point (e.g. batteries have dropped, so the charger starts at full current). That sudden 3–5 kW step can further distort the generator output, causing another trip — a self-reinforcing cycle that can drain fuel at 0.8–1.2 gal/hr without delivering meaningful battery charge. This failure mode is most common with SMA inverters paired with generators lacking an AVR that holds THD below 5% across all loads. The Sungrow, with its 8% THD threshold, rarely enters this loop on the same generator.
Sungrow The SG-RT series does not have a dedicated “Secure Power Supply” (SPS) port; during a grid outage, the inverter will not provide AC power unless paired with a battery (hybrid model). However, when a generator is the sole source, the Sungrow continues to charge the battery (if present) as long as the generator feed stays within the thresholds above.
SMA SMA’s Sunny Tripower X offers a Secure Power Supply function that delivers up to 1920 W from the PV array even without battery, via a dedicated outlet. But: this function requires a stable grid-like waveform — it is not designed to run from a noisy generator. If you attempt to feed SPS through a generator, the inverter’s own voltage sensing may see the generator as “grid” and attempt to synchronise, often failing due to THD >5%.
Worked consequence: In practice, SMA’s SPS is useful only if you have a clean inverter-generator or grid; for a noisy 20 kW diesel, the SPS will either not engage or will cycle off/on. Sungrow doesn’t offer SPS, but its generator ride-through is more reliable for the majority of backup situations where the generator is the main power source.
Reversal: If you install a line-interactive UPS or an automatic voltage regulator between the generator and the SMA inverter (cost ~$800–1200), you can keep THD below 4% and use SPS without issues. That adds cost and complexity but is a viable path for those who want both SMA’s output quality and generator compatibility.
Topology/standards per the cited standards; all product ratings are manufacturer-stated values from the cited datasheets, current to 2026-06; derived/illustrative figures are labelled as such. This is not an independent head-to-head test. Sungrow is a brand affiliated with this site; competitor names are used for identification only.
Leave a Reply
Your email address will not be published. Required fields are marked